Memorial's complete backup-power failure

Five Days at Memorial

Memorial's complete backup-power failure was the decisive breakdown of a system that hospital leaders had already been warned was vulnerable to flooding. In the early hours of August 31, 2005, after two days of emergency operation, the last of the hospital’s generators surged and died. The blackout was not simply a loss of light: it exposed how dependent patient care was on a complicated electrical network whose weakest components lay close to the floodwater, and whose failure began disabling equipment and routines throughout the building.

A vulnerability identified in advance

After Hurricane Ivan nearly struck in September 2004, plant operations director Eric Yancovich attended a meeting with the Army Corps of Engineers and studied storm-surge models. They suggested that a Category Four or Five hurricane could drive twelve to fifteen feet of water around Memorial, which stood three feet below sea level. Yancovich then sketched the elevations of hospital entrances and critical outdoor equipment on lined paper, measuring them against Magnolia Street behind the hospital. His calculations showed that less than four feet of street flooding could send water over the loading dock and into the building.

The generators themselves were on the second floor, but the electrical distribution system was not equally protected. Some emergency-power components, including transfer switches, were at or below ground level. Yancovich warned his supervisor that relatively little water could disable most of the Medical Center and predicted that the main hospital would lose power, forcing patients to be moved to the newer Clara Wing, where he believed the electrical circuitry was better protected. The department had added floodgates and raised the vent for the underground diesel tanks, but more extensive work remained undone. Yancovich recommended elevating ground-level and basement transfer switches, as well as pumps supplying medical air and vacuum suction. A partial bid for electrical work exceeded a quarter of a million dollars; with capital scarce, he expected no immediate approval and kept the proposal on file.

That warning makes the eventual blackout more than an unpredictable equipment mishap. The hospital’s emergency supply depended not only on elevated generators but also on the lower-lying switches and distribution equipment that connected them to the building. As floodwater reached those vulnerable parts, the generators could not by themselves guarantee that power would reach the patients and systems that needed it.

A system under strain

Memorial had three teal-colored generators, each rated at 750 kilowatts and taller than an adult. They fed a network of lines, riser circuits, and transfer switches shaped by successive additions to the original 1926 hospital. Normally, an outside company serviced the machines; on-site maintenance staff mainly changed the oil and ran brief monthly tests. Those tests reflected standards designed for generators supporting vital functions for minutes or hours, not days. Yet Memorial’s disaster plan expected them to carry the hospital for at least three days. By the time the failures escalated, they had already been running for two.

No electrician or engineer on site was a generator mechanic. When one engine stopped earlier, staff concluded that it had overheated. Working by flashlight, they added water to its radiator and restarted it. Later, low oil pressure appeared to be the problem. Maintenance workers brought in barrels of diesel to prime the motors and went across the bridge to the surgery building for additional fuel. Meanwhile, some parts of the hospital lost power, while light in other areas dimmed.

As one generator failed, workers tried to transfer some of its load to another. In rubber boots, they waded through knee-deep basement water and climbed to the mezzanine of the core electrical building. About a third of the automatic transfer switches were at a low level, and the water suggested that switches and associated distribution panels might already be submerged. The workers traced the outage through a narrow passage lined with electrical panels and a warning sign, then used a flashlight to find a yellow-handled bypass lever above their heads. They operated it despite the risk of electrocution, temporarily grafting the failed generator’s load onto a working unit.

The attempted workaround brought its own danger. A gauge showed that the working engine was drawing excessive current, suggesting a short circuit. A fire would have been especially threatening because the sprinkler pumps were underwater and city fire trucks were presumed out of service. Workers separated the loads and went through the hospital shutting off branch circuits to unused fixtures and equipment. When another generator failed, they had a better idea of the cause but no spare parts; an attempt to salvage parts from the failed unit did not work.

The blackout and its immediate effects

The struggle lasted about two hours. At roughly two in the morning on Wednesday, August 31, nearly forty-eight hours after Katrina made landfall near New Orleans, the last backup generator surged and died. Ewing Cook, trying to rest in his second-floor office, heard the sudden silence as the sickest sound of his life. The hospital’s remaining mechanical and electronic supports were now on borrowed time.

Alarms flashed and wailed on the eighth floor, where intensive-care nurses had settled near their rescued patients. Nurse manager Karen Wynn climbed onto a chair and struck an alarm panel with her shoe to silence it, then told the nurses to try to sleep. On the seventh floor, the LifeCare notepad computer lost its text-messaging connection. The special mattress supporting Emmett Everett deflated. Ventilators continued to deliver rhythmic mechanical breaths, but only while their battery backups lasted.

On the fifth floor, dim light from Toshiba Satellite laptop screens was enough for night-shift nurse Michelle Pitre-Ryals to enter notes into electronic charts before the computers’ batteries died. Once the system shut down, those records would be inaccessible; paper, in that moment, was the more dependable technology. The electronic medication-dispensing cart posed a different problem: it would stop working with its stock of medicines locked inside.

The blackout also formed part of a communications breakdown around evacuation. Pitre-Ryals carried a cell phone belonging to a nurse whose husband was at the Coast Guard station. A Coast Guard auxiliary member called to say that three helicopters had been sent and someone was waving them away. Pitre-Ryals took the phone downstairs to the command team, but a nursing director told her not to bring it down again, saying the caller was not part of their evacuation plan. The episode did not restore power or resolve the competing channels of information; it showed how, in the same emergency, a functioning phone could carry an offer of help while command decisions kept that offer at a distance.

Significance and aftermath

The failure laid bare the difference between having generators and having a resilient emergency-power system. Memorial’s machines had been expected to sustain the hospital for days despite being designed and routinely tested for shorter periods; their fuel, maintenance, electrical connections, submerged switches, pumps, and downstream devices all belonged to the same fragile chain. The hand-drawn elevation study and the unapproved work proposal made that chain’s vulnerability visible before Katrina. Once the switches and distribution panels were threatened by water, troubleshooting became a hazardous effort to keep individual circuits alive rather than a reliable means of restoring the hospital as a whole.

The blackout also made the consequences of infrastructure failure tangible at the bedside: a deflating mattress, ventilators dependent on batteries, records being copied before laptops died, and medication sealed inside an inoperative cart. These disruptions unfolded within the broader crisis at Memorial, and staff later carried the trauma of those days in different ways. Gina Isbell described poor sleep, nightmares about her patients, and lasting anger that help had come too slowly; Karen Wynn found that preparing to discuss the events could make her feel as though she were reliving them. Their later distress cannot be reduced to the generator failure alone. But the blackout stands as a concrete turning point in the hospital’s crisis: the known weakness of the power system became a lived emergency, and the machinery that had temporarily held the building together could no longer do so.